Electronic differential pressure measurement for level monitoring

Differential pressure measurement is widely used as a method for monitoring the amount of closed vessels. In many cases, operators use individual instruments with an output signal or on-site display. In contrast, a more precise and fault-immune solution may be the measuring arrangement developed by WIKA using two process transmitters in a primary-secondary relationship.
Each level monitoring application using differential pressure measurement is based on the following principle: For the level of the contents in the vessel, the differential pressure between your liquid and the gaseous phase is determined. Furthermore, the hydrostatic pressure, the precise density of the medium and the vessel geometry are contained in the calculation. Typical measuring instruments have two adjacent process connections for the pressures P1 and P2. For level measurement, a capillary has to bridge the pronounced distance between your two measuring points.
Measurement with two process transmitters as Primary instrument (right) and Secondary instrument. This measuring arrangement for level monitoring may be used flexibly, e.g. for information on the mixing ratio of liquids.
Connection via signal cable
When monitoring the level using electronic differential pressure measurement, however, both measuring points have one process transmitter each. For instance, the WIKA models CPT-2x and IPT-2x are ideal for this. The two transmitters are arranged as Primary instrument and Secondary instrument. They are connected, purely electrically, with a signal cable and are therefore not susceptible to disturbances. The Primary instrument supplies the Secondary instrument with power. The Secondary instrument is parameterised via a serial interface or through the display on the Primary instrument. Finally, communication takes place via an interior bus.
Level monitoring in a closed tank
Application example
The figure on the left shows a typical application example for level monitoring with electronic differential pressure measurement on a liquid tank. The Secondary instrument measures the pressure P1, in this case the gas pressure, and transmits it to the Primary instrument. This detects the pressure P2, here the pressure in the liquid column in the bottom of the tank. THE PRINCIPAL instrument calculates the differential pressure from P1 and P2. Utilizing the measured value and taking into account the other parameters mentioned, it determines the quantity in the tank as an indication of the level. This value could be output either being an analogue or digital signal to the control room and/or to the display of the principal instrument.
Advantages of the measuring arrangement with two process transmitters
The technique for level monitoring described here has several advantages in comparison with a conventional method, for instance, with a differential pressure transmitter:
Higher accuracy and ?turndown?
Process transmitters deliver higher degrees of accuracy. Regarding the WIKA models, these are up to 0.05 % of the set span. In addition, there is the possibility of ?turndown?, the average person setting of a specific measuring span (that is also possible retrospectively with instruments which are already installed.)
Minimised temperature effect
Transmission via signal cable with electronic differential pressure measurement minimises the temperature effect. On the other hand, the capillaries used in the conventional measuring method are much more susceptible here. This, in turn, can ultimately affect the measuring result.
Fast commissioning
The electronic measuring arrangement can be commissioned faster. Unlike pressure gauge 10 bar with capillaries, it generally does not require any test run.
Reduced maintenance effort
The maintenance effort is lower: In the event of a fault, only the procedure transmitter concerned should be replaced. On the other hand, with measuring differential pressure with capillaries, the complete measuring arrangement must be replaced.
Note
Further information on the model CPT-2x and IPT-2x process transmitters, which are suitable for electronic differential pressure measurement for level monitoring, can be acquired on the WIKA website.